BWC MEDGAS / KNOWLEDGE
Knowledge & Resources

Practical technical guidance for planning medical gas installations, selecting components and preparing accurate enquiries.

Anaesthetic Gas Scavenging Systems

AGSS Disposal Capacity for Multiple Operating Theatres: Flow and Diversity Worksheet

Create a design review schedule combining anaesthesia workstation requirements, simultaneous room use, terminal limitations, network resistance and dedicated extraction-plant duty.

AI-generated editorial equipment image: AGSS Disposal Capacity for Multiple Operating Theatres: Flow and Diversity Worksheet
AGSS Disposal Capacity for Multiple Operating TheatresBWC Medgas · AI-generated equipment illustrationAI-generated editorial equipment image. Illustrative context, not a product specification or project record.

A central anaesthetic gas scavenging disposal system may serve several operating theatres and procedure rooms, each with its own anaesthesia workstation and local terminal. Choosing the extraction plant from the number of wall outlets alone can be just as misleading as choosing it from the number of pumps on a supplier's frame.

The project must define the required disposal performance across realistic simultaneous clinical activity, then verify that the power device, distribution pipework and terminal units remain within their approved operating limits.

Establish the actual served locations

Begin with an issued room-and-equipment schedule: theatre, pendant position, anaesthesia machine model, intended scavenging use, terminal type and the design authority's future provision. Include procedure rooms only where the hospital's approved anaesthetic services plan requires scavenging.

Do not assume every room is used continuously or that a universal diversity factor is acceptable. Simultaneous use and emergency conditions are decided by the healthcare design team, not inferred from general building occupancy.

The design input matrix

FieldSite-specific inputEvidence needed
Rooms/terminalsNumber and actual location of AGSS connection pointsClinical/architectural drawings
Workstation typesExact anaesthesia machine and scavenging interfaceManufacturer IFU/data
Permitted flow envelopeSupported interface and receiving-system conditionsWorkstation datasheets
SimultaneityApproved operating scenarios and diversityClinical use plan
Distribution networkRoute, branches, resistance and elevation where relevantAGSS designer calculations
Power deviceEffective duty under the system's operating conditionsManufacturer performance curve
Standby/availabilityProject resilience and maintenance strategyApproved risk assessment
DischargeEnvironmental routing and outlet conditionsBuilding-services design
AcceptanceInstalled functional test cases and test pointsCommissioning specification

The table becomes the shared basis for technical comparison; a single catalogue flow number is not enough.

Distinguish free-air capacity from operating duty

The extraction plant supplier may quote an unrestricted fan or blower flow at a nominal condition, but the installed system has resistance through pipes, bends, terminals and any required control components. The effective flow across the required operating range is what matters.

ISO 7396-2:2007 addresses performance and testing of the disposal system, while ISO 9170-2:2008 concerns the terminal interface. Neither justifies treating a zero-resistance blower rating as verified delivery to every theatre.

Treat over-extraction as a design concern too

Scavenging is not necessarily improved by applying unlimited suction. The anaesthesia workstation's protected receiving/transfer arrangement must prevent unsafe effects on the patient breathing system and remain compatible with the connected disposal system.

ISO 80601-2-13:2022 provides the workstation safety boundary. The system designer needs to confirm both the low and high ends of permitted performance, not simply the largest possible extraction flow.

Example: unequal rooms, equal-looking outlets

A hospital proposes six identical AGSS terminals. Four will serve full operating theatres while two connect to specialist procedure spaces with different equipment interfaces and operating patterns. Two vendor quotes each state a six-outlet capacity, without identifying the workstation conditions or simultaneous-use case.

Return the room schedule to bidders and request capacity curves, network calculation assumptions, terminal model compatibility and acceptance points against the same scenario. The number six is not a technical design.

Resilience and service planning

The designer must explain whether duty/standby equipment is required, what happens if the normal extraction unit fails and how maintenance affects clinical operating-room availability. More than one fan does not automatically prove continuity if the electrical/control/discharge path is shared.

Clinical leadership should approve the service availability requirements and any operational contingencies. Do not instruct facilities personnel to test failure conditions by switching off a live AGSS during surgery.

Tie factory evidence to installed performance

A factory test may establish one power device's curve or assembly function. A site test must verify the commissioned arrangement, including actual terminal positions and the relevant receiving interfaces.

The NHS Scotland SHTM 02-01 (2026) lists Form A17 for AGSS tests, with project details and acceptance governed by the adopted local procedures. NHS England HTM 02-01 provides the broader current UK design and verification guidance.

Procurement checklist

Request a room schedule, workstation interface limits, rated terminal variants, complete plant duty curve, maximum installed operating envelope, noise/energy characteristics, standby and control concept, discharge design, commissioned test plan, spare-part availability and explicit exclusions.

BWC Medgas can quote selected terminal fittings and medical gas installation accessories when the AGSS interface and exact approved model are defined. Complete extraction-plant capacity calculations are the responsibility of the appointed specialist.

Send the approved AGSS terminal/interface requirement to BWC Medgas.

Frequently asked questions

Can a six-outlet AGSS always serve six simultaneous anaesthesia workstations?

Not without proving the required simultaneous-duty case and each workstation's permitted operating conditions.

Does a larger blower automatically make the system safer?

No. Excessive extraction and the anaesthesia workstation interface must also be assessed.

Primary technical references

CONTACT BWC MEDGAS

Tell us what your project requires.

Share your product list or specifications and we will discuss the options.

WhatsApp